Advanced Refrigeration Podcast podcast

Divorce Signed Valves Oversized CO2 Rack Chaos, Flash Gas Tricks & Why Pulse Valves Hunt Episode 547 Video

0:00
44:26
Rewind 15 seconds
Fast Forward 15 seconds

Divorce Signed Valves Oversized CO2 Rack Chaos, Flash Gas Tricks & Why Pulse Valves Hunt Episode 547

Brett announces his divorce is finalized after mediation and jokes about signing over the podcast, then he and Kevin recap a Target trim-out stalled because electricians left wiring incomplete, pushing the job back weeks. The episode shifts into CO2 rack troubleshooting on a small medium-temp rack where oversized Danfoss AKV valves cause low-superheat shutdowns, suction pressure instability, and hunting; by graphing every 15 seconds they catch the valve cycling and trace the issue to an AKV 15-2 installed instead of the intended smaller valve, leading to oversized capacity and “death spiral” short cycling. They discuss why valves control better when more loaded, critique pulse valves, and explain how manipulating gas cooler outlet temperature increases flash gas to add load on low-load winter conditions, using pH diagram examples and flash-gas flow rates. They argue for better gas cooler fan control, split gas cooler designs, EPR use, and avoiding oversized variable-speed compressors.

More episodes from "Advanced Refrigeration Podcast"