Fast Recovery On Gas Coolers Copeland & Danfoss, More Programming Tips - Episode 546 Audio
Fast Recovery On Gas Coolers Copeland & Danfoss, More Programming Tips - Episode 546
CO2 Rack Fast Recovery: Danfoss Fan Override Hack + Copeland E3 Gas Cooler Setup (With Compressor Chaos)
In this episode of the Advanced Refrigeration Podcast, Brett Wetzel and Kevin Compass bounce between dark humor and real-world chaos—starting with Kevin's exhausting compressor swap that turns into a full-blown cluster of wrong parts, impossible bolts, frame welding, and repiping. From there, they tackle a common CO2 rack headache: after a shutdown, cold ambient temps can keep gas cooler fans from ramping up, causing high-pressure trips. Brett walks through a Danfoss workaround by forcing fan speed via a digital input tied to a pressure-switch logic using medium-temp discharge pressure, noting the frustrating need for physical I/O. They then compare it to a quicker Copeland E3 approach, discuss floating temperature control limits, fast recovery setup, PID tuning to prevent hunting, and why poor gas cooler/HP valve control makes the whole rack run like trash.