Software Architecture Insights podcast

Redundancy Assumes Independence

0:00
10:36
Reculer de 15 secondes
Avancer de 15 secondes

On the 1st of September, a technician walked into a Google data center in Iowa to swap out optical transceivers. Routine work. They removed one fiber cable, then another, then another.

Thirteen minutes later the us-central1-b zone was isolated, and it stayed that way for four hours and eleven minutes. More than 15 Google Cloud products went with it.

The headline version of this story is wrong. The redundancy was real and it was working: multiple routers, separate fiber paths, independent power. It did nothing — because redundancy math assumes failures don't know about each other, and a maintenance procedure knows about all of them.

In this episode:

  • What Google actually wrote, and the one word in their report doing all the work
  • Why a procedure that visits every redundant element in sequence makes them perfectly correlated
  • Four hours of outage, nineteen minutes of repair: the diagnostic gap in physical-layer failures
  • The zone that never looked dead from the inside, and why multi-zone failover didn't fire
  • Health checks that never leave the building
  • Finding your correlated maintenance: the list that isn't your single-points-of-failure list

Links:


D'autres épisodes de "Software Architecture Insights"